Permit Number: T16CM07666
Parcel: 130140260

Address:
4150 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM07666
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. MOST OF THE SHEETS IN THIS SUBMITTAL DO NOT MEET THAT STANDARD. PLEASE REVISE.
2. SHEET A1.1; PLAN 101: PER THE IBC SECTION 1109.11, AT LEAST 5% (AND NOT LESS THAN 1) OF THE SEATING SPACES SHALL BE ACCESSIBLE. PLEASE INDICATE ON THE PLAN THE LOCATION OF THE ACCESSIBLE SEATING AS REQUIRED.
3. SHEET F1; PLAN: PLEASE REMOVE THE CLOUD AT THE FLORAL/BAKERY/DELI AREA, OR INDICATE ON THE PLAN THIS IS THE AREA FOR THE SCOPE OF WORK.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/04/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: The minimum font size is 3/32".]