Permit Number: T16CM07658
Parcel: 126180560

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T16CM07658
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2016 TWEIDEM1 ZONING REVIEW Passed
10/06/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM07658

PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
DIAGRAMS / CALCULATIONS:

1. Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). The distribution panel bus and extended bus conductor (4) requires a rating for receiving electrical power from two sources. Show the panel rating and a minimum 217 AMP feeder rating when placed between source breakers of 200A & 60A. (217A conductor x 120% equal or greater than 200A + 60A), or move the backfeed breaker to the service panel.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
10/06/2016 TWEIDEM1 ENGINEERING REVIEW Denied