Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM07621
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/06/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/06/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
10/06/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/06/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
10/06/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A0.0; CODE REVIEW: A NOTE AT THE BOTTOM OF THE CODE REVIEW REFERENCES THE IBC SECTION 412.1.1.1 FOR THE SEPARATION OF THE NEW FIRE PUMP ENCLOSURE. PLEASE REVISE THE REFERENCE. 2. SHEET A0.1; SITE KEYNOTES (NOTE 1): PLEASE REVISE THE REFERENCE PER COMMENT 1. 3. SHEET S1.0; KEYNOTES: NOTE 4 INDICATES THENEW TANK MAY BE PLACED ON THE EXISTING SLAB IF THE SLAB IS 'STRUCTURALLY SOUND'. WHO DETERMINES THAT CONDITION? PLEASE VERIFY. 4. SHEET S2.0; DETAIL 103: THE TITLE INDICATES A MASONRY WALL BUT IS SHOWN AS A CAST IN PLACE CONCRETE WALL. PLEASE VERIFY. 5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
10/06/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
10/06/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
10/06/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/11/2016 | KROBLES1 | FIRE | REVIEW | Needs Review |