Permit Number: T16CM07621
Parcel: 115180220

Address:
1501 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07621
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2016 STEVE SHIELDS ZONING REVIEW Approved
10/06/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/06/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/06/2016 LOREN MAKUS ENGINEERING REVIEW Approved
10/06/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A0.0; CODE REVIEW: A NOTE AT THE BOTTOM OF THE CODE REVIEW REFERENCES THE IBC SECTION 412.1.1.1 FOR THE SEPARATION OF THE NEW FIRE PUMP ENCLOSURE. PLEASE REVISE THE REFERENCE.
2. SHEET A0.1; SITE KEYNOTES (NOTE 1): PLEASE REVISE THE REFERENCE PER COMMENT 1.
3. SHEET S1.0; KEYNOTES: NOTE 4 INDICATES THENEW TANK MAY BE PLACED ON THE EXISTING SLAB IF THE SLAB IS 'STRUCTURALLY SOUND'. WHO DETERMINES THAT CONDITION? PLEASE VERIFY.
4. SHEET S2.0; DETAIL 103: THE TITLE INDICATES A MASONRY WALL BUT IS SHOWN AS A CAST IN PLACE CONCRETE WALL. PLEASE VERIFY.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/06/2016 ROBERT SHERRY WATER REVIEW Completed
10/06/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/06/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/11/2016 KROBLES1 FIRE REVIEW Needs Review