Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T16CM07589
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comment. Also provide a written response. #1. The feeder conduit, conductor sizes are undersized for the 100 amp OCPD's for CW-4, CW-5, CW-6. Ref; NEC art 310.15, 250.122 , 430. |
10/05/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify that the location of the refrigerant relief valve termination complies with the requirements of Section 105.7, IMC 2012. |