Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM07589
Parcel: 11712098A

Address:
1 S CHURCH AV

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM07589
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comment. Also provide a written response.
#1. The feeder conduit, conductor sizes are undersized for the 100 amp OCPD's for CW-4, CW-5, CW-6. Ref; NEC art 310.15, 250.122 , 430.
10/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that the location of the refrigerant relief valve termination complies with the requirements of Section 105.7, IMC 2012.