Permit Number: T16CM07587
Parcel: 12308022A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07587
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2016 STEVE SHIELDS ZONING REVIEW Approved
10/04/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/04/2016 ROBERT SHERRY ELECTRICAL-COMMERCIAL REVIEW Passed
10/04/2016 ROBERT SHERRY WATER REVIEW Completed
10/04/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. THIS IS ADDITION OF OCCUPIED SPACE FOR THE EXISTING BUILDING. A NEW CODE ANALYSIS WILL BE REQUIRED FOR THIS TENANT IMPROVEMENT. PLEASE INCLUDE.
2. PLEASE PROVIDE A VALUATION FOR THE ADDITION OF THE NEW 600 SF TO THE EXISTING BUILDING.
3. PLEASE VERIFY THE NEW OCCUPANT LOAD DOES NOT CHANGE THE NUMBER OF REQUIRED PLUMBING FIXTURES. PROVIDE THOSE CALCULATIONS ON THE DRAWINGS.
4. PLEASE INCLUDE A NEW MEANS OF EGRESS ANALYSIS ON THE DRAWINGS.
10/04/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/04/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/07/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
10/07/2016 KROBLES1 FIRE REVIEW Needs Review