Permit Number: T16CM07574
Parcel: 129020510

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07574
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2016 STEVE SHIELDS ZONING REVIEW Approved
10/04/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
10/04/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also include a written response.
#1. Ref; plan sheet E0.1. Keynote #8, the 1/0 feeders are under sized for 200 amp OCPD. NEC 310.15. Also include the new oven in the load calc's.
10/04/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
10/04/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A4.0; DETAIL 3: PLEASE PROVIDE THE WEIGHT OF THE WATER CHILLER.
2. SHEET A4.0; DETAIL 3: PLEASE PROVIDE THE ANGLE SIZE FOR THE CHILLER SUPPORT. INCLUDE THE NUMBER OF SUPPORTS REQUIRED (OR THE SUPPORT SPACING).
3. SHEET A4.0; DETAIL 3: PLEASE INDICATE ON THE DETAIL HOW THE CHILLER SUPPORT KICKERS ARE CONNECTED TO EACH OTHER (WELDED/BOLTED?).
10/04/2016 ROBERT SHERRY WATER REVIEW Completed
10/04/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
10/04/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/05/2016 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2016 BGRANT1 OUT TO CUSTOMER Completed