Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM07574
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/04/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/04/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
10/04/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also include a written response. #1. Ref; plan sheet E0.1. Keynote #8, the 1/0 feeders are under sized for 200 amp OCPD. NEC 310.15. Also include the new oven in the load calc's. |
10/04/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
10/04/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A4.0; DETAIL 3: PLEASE PROVIDE THE WEIGHT OF THE WATER CHILLER. 2. SHEET A4.0; DETAIL 3: PLEASE PROVIDE THE ANGLE SIZE FOR THE CHILLER SUPPORT. INCLUDE THE NUMBER OF SUPPORTS REQUIRED (OR THE SUPPORT SPACING). 3. SHEET A4.0; DETAIL 3: PLEASE INDICATE ON THE DETAIL HOW THE CHILLER SUPPORT KICKERS ARE CONNECTED TO EACH OTHER (WELDED/BOLTED?). |
10/04/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
10/04/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
10/04/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/05/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/06/2016 | BGRANT1 | OUT TO CUSTOMER | Completed |