Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM07524
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/11/2016 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 10/13/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/13/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the specified sensor faucets for the public lavatories will dispense a maximum of 0.25 gallons per metering cycle and that the faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. 2. Verify that the "or equivalent" mixing valves specified for the public lavatories will be listed to ASSE 1070. Reference: Section 607.1.2, IPC 2012. 3. Verify that the installation of the expansion tank (detail 7/P2.1) with a check valve between the expansion tank and the water heater complies with the manufacturer's instructions. Reference: Sections 303.2 and 607.3, IPC 2012. 4. Provide a vent for P-1 in room 109. Reference: Section 901.2.1, IPC 2012. |
| 10/14/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify why FC-1 and FC-2 are noted as each having a design outside air flow rate of 250 CFM on sheet M3.1 but the air balance schedule on sheet M1.1 calls for each being balanced for 150 CFM of outside air. Similarly, FC-5 and FC-6 are noted as each having a design outside air flow rate of 350 CFM on sheet M3.1 but the air balance schedule on sheet M1.1 calls for each being balanced for 175 CFM of outside air. Reference: Section 107.2.1, IBC 2012. 2. Provide the balancing data for room 104. Reference: Section 107.2.1, IBC 2012. 3. Clarify the return air flow rates for FC-11; four air flow rates are noted but there are only three return air grilles. Reference: Section 107.2.1, IBC 2012. 4. The balancing data for FC-10 appears to indicate that corridor 110 is being used as a duct. Reference: Section 601.2, IMC 2012. |
| 10/26/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/27/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 10/27/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G1.1; PROJECT DATA (APPLICABLE CODES): PLEASE REVISE THE FIRE CODE TO THE 2012 IFC AND REVISE THE ELECTRICAL CODE TO THE 2011 NEC. 2. SHEET G1.1; PROJECT DATA (APPLICABLE CODES): PLEASE REVISE THE ICC/ANSI A117.1 TO THE 2009 EDITION AND REMOVE THE 2010 ADAAG REFERENCE. 3. SHEET G1.2; PLUMBING FIXTURES: PLEASE REVIEW THE PLUMBING FIXTURE REQUIREMENTS. FOR 70 MALES AND 70 FEMALES, THE WATER CLOSETS REQUIRED FOR A B OCCUPANCY ARE 3 PER SEX, THE LAVATORIES ARE 2 PER SEX, THE DRINKING FOUNTAINS ARE 2 (AS NOTED), AND THE SERVICE SINK IS 1 (AS NOTED). IF IT IS INDICATED ON THESE REQUIREMENTS THAT THE TWO RESTROOMS IN THE ASSEMBLY AREA ARE TO BE USED, YOU CAN REDUCE THE CALCULATION YOU HAVE INDICATED TO SHOW THE PLUMBING REQUIREMENTS ARE SATISFIED. 4. SHEETS G1.2, A2.2, AND A3.1; PLANS: PLEASE PROVIDE A NORTH ARROW ON THESE PLANS. 5. SHEET G1.2; PLAN: DOES THE EXIT NEAR GRIDS 4 AND A.7 ENTER INTO AN EXISTING BUILDING? PLEASE VERIFY. IF SO, PLEASE VERIFY THE REQUIREMENTS OF THE IBC SECTION 1014.2 ARE MET, AND A DISCERNIBLE PATH OF EGRESS TRAVEL TO AN EXIT IS PROVIDED. 6. SHEET G1.2; CODE REVIEW: PER THE IBC SECTION 1105.1, AT LEAST 60% OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE. PLEASE VERIFY ON THE DRAWINGS THIS PLAN MEETS THAT REQUIREMENT. 7. SHEET G1.2; PLAN: VERIFY THE PATH OF EGRESS TRAVEL TO EXITS ARE MARKED PER THE REQUIREMENTS OF THE IBC SECTION 1011.1. REVISE THE PLAN AS REQUIRED. 8. SHEET G1.2; PLAN: PLEASE INDICATE ON THE PLAN THE EXIT ACCESS TRAVEL DISTANCES (AS SHOWN IN THE CODE REVIEW) MEET THE REQUIREMENTS OF THE IBC TABLE 1016.2. 9. SHEET A2.1.1; FLOOR PLAN GENERAL NOTES: NOTES 3 AND 4 SHOULD REFERENCE SHEET A2.4 FOR DOOR AND WINDOW TYPES. PLEASE REVISE. 10. SHEET A6.1: PLEASE ADD THE HIGH/LOW DRINKING FOUNTAIN ELEVATION TO THIS SHEET PER THE ICC/ANSI FIGURE 602.5. 11. GENERAL: IS THIS PROJECT A FIRST TENANT IN TI (FIRST TENANT TO OCCUPY THIS SPACE)? PLEASE VERIFY. 12. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |