Permit Number: T16CM07518
Parcel: 10819019H

Address:
715 E WETMORE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM07518
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/07/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The submitted detail does not show the existence of a shut off valve for the cold water to the water heater, it is not clear how the water filtration system relates to the cold water supply to the water heater (i.e. se detail 2, P1102), and the font size is less than the required minimum of 3/32". [Initial comment: Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503, 504, 606.1, 607.2, and 607.3, IPC 2012.]
2. Provide a reduced pressure principle backflow preventer (ASSE 1013) for the cold water connection to the misting system. [Initial comment: Appliances (e.g. coffee makers, espresso machines, misting system, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1, 608.3, and 608.16.1, IPC 2012.]
12/07/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed