Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM07518
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/02/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/07/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The submitted detail does not show the existence of a shut off valve for the cold water to the water heater, it is not clear how the water filtration system relates to the cold water supply to the water heater (i.e. se detail 2, P1102), and the font size is less than the required minimum of 3/32". [Initial comment: Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503, 504, 606.1, 607.2, and 607.3, IPC 2012.] 2. Provide a reduced pressure principle backflow preventer (ASSE 1013) for the cold water connection to the misting system. [Initial comment: Appliances (e.g. coffee makers, espresso machines, misting system, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1, 608.3, and 608.16.1, IPC 2012.] |
| 12/07/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |