Review Details: COMMERCIAL - TI

Permit Number - T16CM07518
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify the existence of a grease waste sewer for the building: the shell drawings do not indicate that one was installed.
2. Revise the gravity grease interceptor calculations based on Section 1003.3(C), IPC 2012 as amended by the City of Tucson; include the mop sink in the calculations.
3. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503, 504, 606.1, 607.2, and 607.3, IPC 2012.
4. Appliances (e.g. coffee makers, espresso machines, misting system, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1, 608.3, and 608.16.1, IPC 2012.
5. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
6. Clarify the reason for using an indirect waste connection for the bar and hand sinks. Reference: Sections 301.3 and 802.1, IPC 2012.
10/12/2016 ROBERT SHERRY WATER REVIEW Completed
10/12/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the specified programmable thermostat requirements to provide the capability of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.2.4.3.3, IECC 2012.
2. The rooftop air conditioners installed as part of the shell construction do not include an economizer. Will this feature be added to the units? Reference: Section C403.3.1.1.4, IECC 2012.
3. The City of Tucson did not adopt ASHRAE Standard 62.1 for ventilation calculations and the 2012 IMC only references the ASHRAE Standard for the purpose of calculating the system ventilation efficiency (Ev). Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012; for HVAC systems serving multiple zones (e.g. AC1-2), see Section 403.3.2.3, IMC 2012.
4. Provide justification for the use of a Zone Air Distribution Effectiveness (Ez) of 1.0 for a ceiling supply, ceiling return using a gas-fired furnace. Reference: Section 403.3.1.2, IMC 2012.
10/24/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/24/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G-0003; EGRESS PLAN: THE NORTH EXIT HAS A NOTE ('EXIT #2; 3'-0" DOOR), BUT A DOUBLE DOOR IS INDICATED. PLEASE CLARIFY.
2. SHEET G-0003; EGRESS PLAN: PLEASE INDICATE A SCALE ON THIS PLAN (PER THE SHEET TITLE BLOCK).
3. SHEET I-1103; FLOOR PLAN: AT THE RESTROOM AREA, THERE IS A WALL TYPE 3 INDICATED AT THE NORTH WALLS OF THE MEN'S AND WOMEN'S ROOMS. THE LEGEND INDICATES GYPSUM SHEATHING ON ONE SIDE ONLY. IS THIS CORRECT (EXPOSED TO VESTIBULE ON NORTH SIDE AND RESTROOM ON SOUTH SIDE)? PLEASE VERIFY.
4. SHEET I-1105; PLAN: PER THE IBC SECTION 1108.2.9.1, AT LEAST 5% (BUT NOT LESS THAN 1) OF THE DINING SURFACES SHALL BE ACCESSIBLE. PLEASE INDICATE ON THIS PLAN THE LOCATION OF THE ACCESSIBLE TABLES (INTERIOR AND EXTERIOR), AND INDICATE THE ACCESSIBLE CLEAR FLOOR SPACES (30" X 48" PER THE ICC/ANSI FIGURE 305.3) AT THOSE TABLES.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/24/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/25/2016 GERRY KOZIOL WWM REVIEW Approved