Review Details: REVISION - - 1ST
Permit Number - T16CM07498
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. Ref: Tucson/Pima County Outdoor Lighting Code. Provide complete compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. #1.The residential option per table 401.1 cannot be used as this project is considered commercial. Option #1, #2, or #3 must be used. #2. Provide a complete luminaire schedule, include lamp color temperature. Not to exceed 3500 Kelvin per sec. 402.1. #3. All the information on the plans as required per sec. 104, PERMIT and PLAN SUBMITTAL REQUIREMENTS including total lumen output on the developed property, with any exceptions that may apply, and if a special inspection is required or not. |