Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM07464
Parcel: 107020080

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T16CM07464
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2016 MARTIN BROWN FIRE REVIEW Approved
10/06/2016 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change DP16-0171 needs to be approved first.
10/10/2016 KROBLES1 ZONING REVIEW Needs Review
10/10/2016 KROBLES1 WATER REVIEW Needs Review
10/18/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change T16CM07464 - PLAN REVIEW COMMENTS
Reviewer: Christopher Anderson, October 12, 2016
BUILDING - COMMERCIAL
Insulation for the exterior walls, fenestration, and roof/ceiling in the conditioned office suite must comply with the prescriptive insulation requirements of 2012 IECC Tables C402.2 and C402.3.
Adjacent to the Window Types elevations add the note. “Per IECC Tables C402.3 fixed fenestration at interior and exterior walls shall have a maximum U-factor of 0.50 and entrance doors shall have a maximum U-factor of 0.83. Windows and entrance doors in exterior walls shall have a SHGC of 0.25.”
Since the warehouse is unconditioned space, the interior walls of the office suite are considered part of the thermal envelope. They shall be insulated with minimum R-13 cavity insulation with a continuous layer of R-5 insulation. Show this on building sections, sheet A3.0, and revise existing keynotes as needed.
The metal building portions of exterior walls at the office suite shall be insulated with minimum R-13 cavity insulation (between studs or girts) and a layer of R-6.5 continuous insulation. The masonry portion of exterior wall shall be insulated with minimum R-6.3 continuous insulation. Show this on building sections, sheet A3.0, and revise existing keynotes as needed.
The ceiling for the office suite must have minimum R-38 cavity insulation. Show this on building sections, sheet A3.0, and revise existing keynotes as needed.
As an option, submit a “passing” building envelope COMcheck for envelope systems other than IECC prescriptive assemblies.
The kitchenette sink in Hall 104 shall be positioned in countertop so that it is centered 24” from south wall of hall to comply with ICC/ANSI A117.1 606.2, exception 6.
On sheet A3.0 add 2’-10” vertical dimension for kitchenette countertop per ICC/ANSI A117.1 902.4.
10/19/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
10/20/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Show the locations of the electric water heaters on the floor plan.
#2. Provide for a 125 volt maintenance receptacle for the mechanical equipment. NEC 210.63
#3. Indicate conduit, conductor sizes and types of the feeders between the service disconnects and the CT can.
#4. Provide complete compliance with the 2012 IECC for lighting.
#5. Luminaire lamp color temperature output is not to exceed 3500K for exterior lighting. Per the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE sec. 402.1.
Ref; 2012 IBC sec 107.2.1, 2011 NEC.
ELECTRICAL - COMMERCIAL
On Lighting and Power Plan, sheet E1.0, add a 15 or 20 amp GFI service outlet for the outdoor mechanical unit, located within 25’ of the unit per NEC 210.63.
10/24/2016 FRODRIG2 PLUMBING-COMMERCIAL REVIEW Reqs Change .
PLUMBING - COMMERCIAL
On sheet P1.0, verify that lavatory faucets specified are automatic and dispense a maximum of 0.25 gallon per metering cycle but will operate for a minimum time of 10-seconds for accessibility. Also verify that kitchenette sink will operate for a minimum time of 10-seconds for accessibility. Reference Section 416.6 IPC 2012 as amended by the City of Tucson, ICC/ANSI A117.1 606.4.
On sheet P1.0 provide domestic water schematic. Include permanent water source for the point of use drinking water dispenser per COT Policy 2008-21 (E).
On sheet P1.0 information in the tankless water heater schedule and schematic conflicts with information regarding the water heater in the Plumbing Fixture schedule. Also, the Plumbing Fixture Schedule only indicates WH-1.

MECHANICAL – COMMERCIAL
On sheet M1.0 show how required outside air ventilation will be supplied to all spaces in the office suite. Notes in the Outside Air Ventilation Schedule remarks column imply that AH1, AH-2 and AH-3 will supply the required OA; however ductless mini-split heat pumps do not have the functionality to do this.
On sheet M1.0 the required 50 CFM OA ventilation supply shall be balanced by the air exhausted to the outdoors. The 50 CFM restroom exhaust fan must be run continuously while the conditioned office suite is occupied.
10/24/2016 FRODRIG2 MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
On sheet M1.0 show how required outside air ventilation will be supplied to all spaces in the office suite. Notes in the Outside Air Ventilation Schedule remarks column imply that AH1, AH-2 and AH-3 will supply the required OA; however ductless mini-split heat pumps do not have the functionality to do this.
On sheet M1.0 the required 50 CFM OA ventilation supply shall be balanced by the air exhausted to the outdoors. The 50 CFM restroom exhaust fan must be run continuously while the conditioned office suite is occupied.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/02/2016 KROBLES1 OUT TO CUSTOMER Completed