Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM07387
Parcel: 133231430

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07387
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2016 ANDREW CONNOR ZONING REVIEW Approved
09/26/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
09/29/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide ventilation calculations for the suite. Reference: Section 403.3, IMC 2012.
2. Provide balancing information for the tenant improvement. Reference: Section 403.7, IMC 2012.
3. Provide general exhaust for the beauty salon. Reference: Section 403.3, IMC 2012.
09/29/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1; FLOOR PLAN: PLEASE REMOVE THE 'ADA' NOTATION FROM BATH #2. THIS BATHROOM DOES NOT MEET THE ACCESSIBILITY REQUIREMENTS OF THE 2009 ICC/ANSI.
2. SHEET A1; GOVERNING REGULATIONS: PLEASE ADD THE 2009 ICC/ANSI A117.1 ACCESSIBILITY CODE TO THE LIST.
3. SHEET A1; CODE REVIEW: THE OCCUPANT LOAD AT THIS REVIEW (54 TOTAL) FOR A B OCCUPANCY TYPE REQUIRES 2 MALE AND 2 FEMALE WATER CLOSETS PER THE IBC TABLE 2902.1. THE OCCUPANCY LOAD SHOULD BE REVIEWED TO CONSIDER THE ENTIRE SPACE AS A B OCCUPANCY TYPE TO REDUCE THE LOAD.
4. SHEET A1; FLOOR PLAN: THE SINK IN THE BREAK ROOM (KEYNOTE 26) IS REQUIRED TO BE ACCESSIBLE PER THE IBC SECTION 1109.4. PLEASE INDICATE A 34" MAXIMUM HEIGHT OF THE SINK AND COUNTER ABOVE FINISH FLOOR.
5. SHEET A1: PER THE IBC TABLE 2902.1 NOTES f AND g, A HIGH/LOW DRINKING FOUNTAIN (OR SINGLE POINT OF USE DISPENSER) AND A SERVICE SINK ARE REQUIRED FOR OCCUPANCY LOADS GREATER THAN 15. PLEASE REVIEW AND REVISE AS REQUIRED.
6. SHEET A1; CODE REVIEW: THE DRAWING INDICATES THE NUMBER OF EXITS FOR AN A-2 OCCUPANCY TYPE IS ONE. TWO EXITS ARE REQUIRED PER THAT TABLE 1015.1 FOR AN 'A' OCCUPANCY TYPE. REMOVE THE NOTE FOR AN A-2 AND CONSIDER ONLY THE B OCCUPANCY TYPE.
7. SHEET A1 (FLOOR PLAN); SHEET A2 (DIMENSION PLAN): KEYNOTE 21 ON SHEET A1 INDICATES A FURR-OUT WALL MAY BE REQUIRED AT THE EAST WALL OF THE BREAK ROOM. THE DIMENSION PLAN ON SHEET A2 MAKES N0 REFERENCE OF THIS. PLEASE ADD.
8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/29/2016 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the serial number and size of the water meter serving this suite and the total demand it serves.
32. Verify that a reduced pressure backflow preventor has been installed after the water meter.
09/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Correct the first plumbing note: this activity is to be designed per the 2012 IPC and the City of Tucson is the jurisdiction.
2. Provide specifications for the new water heater.
3. Provide a detail for the installation of the water heater showing the required valves and the correct installation of the expansion tank.
4. Verify that all of the plumbing fixtures being installed have a 3rd party listing.
5. The fixture drain for the washing machine shall connect to a minimum 3" horizontal drain. Reference: Section 406.2, IPC 2012.
6. Verify that all of the new cleanouts are sized for the pipes they serve. Reference: Section 708.7, IPC 2012.
7. Verify that the temperature and pressure relief for the new water heater does not have a trapped section. Reference: Section 504.6, IPC 2012.
09/29/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/05/2016 RBENT2 FIRE REVIEW Needs Review