Permit Number: T16CM07383
Parcel: 133243720

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM07383
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 4: THE WRAP LISTED FOR THE FIRE PROTECTION OF THE DUCTS INTO THE GAS STORAGE MAY NOT BE SUBSTITUTED FOR A RATED SHAFT. PLEASE PROVIDE A ONE HOUR RATED SHAFT FOR BOTH DUCTS ENTERING THE GAS STORAGE ROOM. IN ADDITION, PLEASE REVISE THE NOTE ON SHEET a2 FOR THE EXHAUST DUCT. ADD A NOTE FOR THE SECOND DUCT INTO THAT ROOM.
09/30/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/30/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change See comments for building

Final Status

Task End Date Reviewer's Name Type of Review Description
10/03/2016 BGRANT1 OUT TO CUSTOMER Completed