Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM07383
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/30/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 4: THE WRAP LISTED FOR THE FIRE PROTECTION OF THE DUCTS INTO THE GAS STORAGE MAY NOT BE SUBSTITUTED FOR A RATED SHAFT. PLEASE PROVIDE A ONE HOUR RATED SHAFT FOR BOTH DUCTS ENTERING THE GAS STORAGE ROOM. IN ADDITION, PLEASE REVISE THE NOTE ON SHEET a2 FOR THE EXHAUST DUCT. ADD A NOTE FOR THE SECOND DUCT INTO THAT ROOM. |
| 09/30/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/30/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | See comments for building |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/03/2016 | BGRANT1 | OUT TO CUSTOMER | Completed |