Permit Number: T16CM07383
Parcel: 133243720

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM07383
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2016 KEN BROUILLETTE FIRE REVIEW Approved
09/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show the location of the zone valves for the O2 and NO2 services.
09/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Using a transfer duct to move the entry point of the return air into the hallway does still results in the hallway being used as a duct. [Initial comment: Revise the ductwork for HP-X1 to avoid using the egress corridor as a duct.]
09/29/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET a2; FLOOR PLAN: A NEW NOTE INDICATES THE GAS STORAGE ROOM REQUIRES ONE HOUR RATED WALLS AND CEILING. PLEASE PROVIDE DETAILS FOR A ONE HOUR FIRE RESISTANCE RATED WALL AND CEILING ASSEMBLY. INDICATE A U.L. RATING NUMBER ON EACH DETAIL.
2. SHEET a2; FLOOR PLAN: THE NEW GAS STORAGE NOTE MUST MEET THE CITY OF TUCSON STANDARDS FOR MINIMUM LETTERING HEIGHT (3/32" MINIMUM FOR UPPER AND LOWER CASE LETTER). PLEASE REVISE.
3. SHEET a2: A NEW DETAIL HAS BEEN ADDED AT THE BOTTOM OF THE SHEET. PLEASE LOCATE THIS ON THE FLOOR PLAN. IF THE SINK AND COUNTER ARE REQUIRED TO BE ACCESSIBLE, THE 3'-0" HEIGHT ABOVE THE FINISH FLOOR SHOULD BE REVISED TO 2'-10"
MAXIMUM.
4. SHEET M2; WORK PLAN (GAS STORAGE ROOM): THE TWO DUCTS INDICATED IN THIS ROOM MUST BE ENCLOSED IN A ONE HOUR FIRE RESISTANCE RATED ASSEMBLY. PLEASE INDICATE ON SHEETS a2 AND M2, AND PROVIDE DETAILS ON THE PLAN FOR THAT ONE HOUR ENCLOSURE ASSEMBLY. INDICATE A U.L. RATING NUMBER FOR THOSE.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.