Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM07383
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/26/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/26/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the ductwork for HP-X1 to avoid using the egress corridor as a duct. |
09/26/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/26/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/26/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/27/2016 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Manifold Med Gas detail (sheet P5) appears to indicate quantities of oxidizing gases exceed amounts allowed by table 105.6.8 of the 2012 International Fire Code. Please indicate how the requirements of section 5306 of the IFC will be met. |
09/27/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
09/27/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
09/29/2016 | RBENT2 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |