Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/26/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the ductwork for HP-X1 to avoid using the egress corridor as a duct.
09/26/2016 ROBERT SHERRY WATER REVIEW Completed
09/26/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/26/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/27/2016 MARTIN BROWN FIRE REVIEW Reqs Change Manifold Med Gas detail (sheet P5) appears to indicate quantities of oxidizing gases exceed amounts allowed by table 105.6.8 of the 2012 International Fire Code. Please indicate how the requirements of section 5306 of the IFC will be met.
09/27/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
09/27/2016 ANDREW CONNOR ZONING REVIEW Approved
09/29/2016 RBENT2 PLUMBING-COMMERCIAL REVIEW Needs Review