Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM07383
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/26/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the ductwork for HP-X1 to avoid using the egress corridor as a duct. |
| 09/26/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/26/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/26/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/27/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 09/27/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 09/27/2016 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Manifold Med Gas detail (sheet P5) appears to indicate quantities of oxidizing gases exceed amounts allowed by table 105.6.8 of the 2012 International Fire Code. Please indicate how the requirements of section 5306 of the IFC will be met. |
| 09/29/2016 | RBENT2 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |