Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM07379
Parcel: 128100530

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07379
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2016 MARTIN BROWN FIRE REVIEW Approved
10/14/2016 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T16CM07379 - PLAN REVIEW COMMENTS
Reviewer: Christopher Anderson, October 13, 2016
BUILDING – COMMERCIAL
Provide plumbing fixture calculations to show compliance with IBC Table 2902.1. Per the demolition plan, two tenant areas have been combined into a single area. It appears that the existing toilet rooms which served a smaller area are not sufficient to accommodate the enlarged tenant space.
The door hardware schedule indicate that a number of egress access doors from the suite will be controlled by card readers and electric strikes and gives an option for either “fail safe” or “fail secure.” IBC 1008.1.9 requires that egress doors be readily openable from the egress side without the use of a key of special knowledge of effort. These doors shall be “fail safe.” Revise hardware schedule.
Provide sizing calculation and detail for folding partition support between new conference rooms 227 and 228.
10/14/2016 FRODRIG2 WATER REVIEW Approved
10/14/2016 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change See building comments.
10/14/2016 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
The interior lighting COMcheck states that open plan office is exempt from allowed interior lighting power calculations. Please identify the 2012 IECC section and paragraph that exempt this space from complying with either Table C405.5.2(1) or C405.5.2(2). None of the exceptions to C405.1 apply to this space.
10/14/2016 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/03/2016 LBOJORQ1 APPROVAL SHELF Completed
11/03/2016 LBOJORQ1 OUT TO CUSTOMER Completed
11/03/2016 LBOJORQ1 REJECT SHELF Completed