Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM07256
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/21/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 09/21/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/21/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete electrical power and lighting plans. City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd; Permit Review; Commercial Permits; Commercial Plan Review. Ref; IBC sec. 107.2.1 ELECTRICAL PLAN REQUIREMENTS 1. Electrical floor plan ? Location of all outlets, fixtures, switches, appliances, panels, motors, disconnects, electrical equipment and service ? Assign circuit to each receptacle, light, appliance, meter, disconnect, electrical equipment and indicate panel number on all home runs 2. Complete single line diagram of service for tenant & building ? Voltage and phase ? Panel and/or transformer size ? Feeder loads ? Rating breakers or fuses including A.I.C. ? Complete fault current analysis ? Total tenant and building service load 3. Provide complete panel schedules ? Panel #, voltage, phase, location & withstand rating ? Bus size, main ? Circuit number ? Breaker size, # of poles, & A.I.C. rating ? # of lights, receptacles, or misc. each circuit by phase ? Load in watts, each circuit by phase ? Total connected load each phase (balance all phases to within 15%) ? Add 25% for continuous load (lights, etc.) and largest motor ? Total KVA load 4. Fixture schedule and fixture cut sheets ? Fixture by letter or symbol ? Number and wattage of lamps & total watts of fixture including ballast ? Type of lamp (incandescent, fluorescent, etc.) ? Type of mounting (flush, surface, etc.) 5. 2012 IECC light budget calculations and luminaries switching 6. Show full compliance with the Tucson Outdoor Lighting Code. #7. All electrical plans to be designed and sealed by a engineer currently registered in the state of Arizona. ARS 32-125, and R4-30-304. #8. Electrical review cannot be completed without the information requested. |
| 09/21/2016 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | PLEASE INDICATE IF THE EXISTING WALLS TO THE NORTH AND WEST OF THIS SPACE ARE FIRE RESISTANT RATED WALLS SEPARATING THIS SPACE FROM THE OTHERS. WAS THIS SPACE A 'B' OCCUPANCY TYPE PREVIOUSLY? PLEASE VERIFY. |
| 09/21/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (drinking fountain and service sink). |
| 09/21/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size, location, and the serial number of the water meter serving this suite. |
| 09/21/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A0.0; OCCUPANCY DATA: THE NOTE ON THIS SHEET INDICATING PLUMBING FIXTURES ARE BASED ON FOUR EMPLOYEES IS NOT VALID UNLESS AN APPEAL IS MADE TO THE BUILDING OFFICIAL. PLEASE REMOVE THIS NOTE UNLESS AN APPEAL IS TO BE MADE. 2. SHEET A0.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES. 3. SHEET A2.1; FLOOR PLAN: PER THE IBC TABLE 2902.1 (NOTES f AND g), DRINKING FOUNTAIN (HI LOW) AND A SERVICE SINK ARE REQUIRED. PLEASE VERIFY. 4. GENERAL: PLEASE INDICATE IF THE EXISTING WALLS TO THE NORTH AND WEST OF THIS SPACE ARE FIRE RESISTANT RATED WALLS SEPARATING THIS SPACE FROM THE OTHERS. WAS THIS SPACE A 'B' OCCUPANCY TYPE PREVIOUSLY? PLEASE VERIFY. 5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 09/21/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/11/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |