Permit Number: T16CM07256
Parcel: 11901076B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07256
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2016 ANDREW CONNOR ZONING REVIEW Approved
09/21/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/21/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete electrical power and lighting plans. City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd; Permit Review; Commercial Permits; Commercial Plan Review.
Ref; IBC sec. 107.2.1
ELECTRICAL PLAN REQUIREMENTS
1. Electrical floor plan
? Location of all outlets, fixtures, switches, appliances, panels, motors, disconnects,
electrical equipment and service
? Assign circuit to each receptacle, light, appliance, meter, disconnect, electrical equipment
and indicate panel number on all home runs
2. Complete single line diagram of service for tenant & building
? Voltage and phase
? Panel and/or transformer size
? Feeder loads
? Rating breakers or fuses including A.I.C.
? Complete fault current analysis
? Total tenant and building service load
3. Provide complete panel schedules
? Panel #, voltage, phase, location & withstand rating
? Bus size, main
? Circuit number
? Breaker size, # of poles, & A.I.C. rating
? # of lights, receptacles, or misc. each circuit by phase
? Load in watts, each circuit by phase
? Total connected load each phase (balance all phases to within 15%)
? Add 25% for continuous load (lights, etc.) and largest motor
? Total KVA load
4. Fixture schedule and fixture cut sheets
? Fixture by letter or symbol
? Number and wattage of lamps & total watts of fixture including ballast
? Type of lamp (incandescent, fluorescent, etc.)
? Type of mounting (flush, surface, etc.)
5. 2012 IECC light budget calculations and luminaries switching
6. Show full compliance with the Tucson Outdoor Lighting Code.
#7. All electrical plans to be designed and sealed by a engineer currently registered in the state of Arizona. ARS 32-125, and R4-30-304.
#8. Electrical review cannot be completed without the information requested.
09/21/2016 LOREN MAKUS ENGINEERING REVIEW Approved
09/21/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A0.0; OCCUPANCY DATA: THE NOTE ON THIS SHEET INDICATING PLUMBING FIXTURES ARE BASED ON FOUR EMPLOYEES IS NOT VALID UNLESS AN APPEAL IS MADE TO THE BUILDING OFFICIAL. PLEASE REMOVE THIS NOTE UNLESS AN APPEAL IS TO BE MADE.
2. SHEET A0.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES.
3. SHEET A2.1; FLOOR PLAN: PER THE IBC TABLE 2902.1 (NOTES f AND g), DRINKING FOUNTAIN (HI LOW) AND A SERVICE SINK ARE REQUIRED. PLEASE VERIFY.
4. GENERAL: PLEASE INDICATE IF THE EXISTING WALLS TO THE NORTH AND WEST OF THIS SPACE ARE FIRE RESISTANT RATED WALLS SEPARATING THIS SPACE FROM THE OTHERS. WAS THIS SPACE A 'B' OCCUPANCY TYPE PREVIOUSLY? PLEASE VERIFY.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/21/2016 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size, location, and the serial number of the water meter serving this suite.
09/21/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (drinking fountain and service sink).
09/21/2016 MARTIN BROWN FIRE REVIEW Reqs Change PLEASE INDICATE IF THE EXISTING WALLS TO THE NORTH AND WEST OF THIS SPACE ARE FIRE RESISTANT RATED WALLS SEPARATING THIS SPACE FROM THE OTHERS. WAS THIS SPACE A 'B' OCCUPANCY TYPE PREVIOUSLY? PLEASE VERIFY.
09/21/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2016 KROBLES1 OUT TO CUSTOMER Completed