Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM07200
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/28/2016 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please provide more information about existing fire sprinkler system. Most systems are designed to an Ordinary Group II hazard classification. Once the top of storage exceed 12'-0" AFF, more water may be required from the sprinkler system. An analysis of the type of materials stored and the capabilities of the existing system must be performed by a licensed sprinkler contractor or an FPE. Additionally, our records indicate this building is overdue on required annual sprinkler inspections and a 5 year check valve inspection. |
10/19/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |