Permit Number: T16CM07133
Parcel: 13419042D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07133
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/15/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify that the specified programmable thermostats are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. (Note: Arizona does not use daylight savings time) Reference: Section C403.2.4.3.3, IECC 2012.
2. Provide calculations demonstrating that RTU-1 will be providing adequate ventilation for the areas it serves. Reference: Section 403.2, IMC 2012
09/15/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/15/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
09/15/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G002: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE ALL ADDENDUM NOTES AND CODE REVIEW NOTES AS REQUIRED.
2. SHEET G002; BUILDING CODE INFORMATION: PLEASE ADD THE 2009 ICC/ANSI A117.1 ACCESSIBILITY CODE TO THIS LIST.
3. SHEET AE101 (FLOOR PLAN); SHEET G002 (WALL TYPES): THE NEW DEMISING WALL ON THE EAST SIDE OF THIS SPACE INDICATES WALL TYPE W3 ON SHEET AE101. THE W3 WALL SYSTEM DESCRIPTION SHOWN ON SHEET G002 IS NOT CORRECT FOR THAT APPLICATION. PLEASE VERIFY AND REVISE AS REQUIRED.
4. SHEET AE401; ELEVATION 11: PLEASE ADD A VERTICAL GRAB BAR PER THE 2009 ICC/ANSI A117.1, FIGURE 604.5.1.
5. SHEET AE401: PLEASE ADD A DETAIL ON THIS SHEET INDICATING ALL GRAB BAR LENGTHS AND LOCATIONS PER THE 2009 ICC/ANSI FIGURE 604.5.1.
6. GENERAL: PLEASE REVISE ALL LETTERING THAT DOES NOT MEET THE 3/32" HEIGHT REQUIREMENT.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/15/2016 ROBERT SHERRY WATER REVIEW Completed
09/15/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the restroom lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
2. Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
09/15/2016 MARTIN BROWN FIRE REVIEW Approved
09/30/2016 KROBLES1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2016 KROBLES1 OUT TO CUSTOMER Completed