Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM07129
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/15/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
09/15/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the exhaust flow rates for the restroom exhaust fans are greater than the supplied air. 2. Verify the sequence of operation for the restroom exhaust fans. |
09/15/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/15/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
09/15/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PLEASE PROVIDE A ROOF FRAMING PLAN AND STRUCTURAL DETAILS ON A FULL SIZE SHEET. PROVIDE INFORMATION FROM THE STRUCTURAL CALCULATIONS ON THIS SHEET, INDICATING THE LOCATION OF THE NEW ROOF TOP UNITS, THE STRUCTURAL MEMBERS AFFECTED BY THE ADDITION OF THE UNITS, AND ALL DETAILS REQUIRED TO MEET THE STRUCTURAL REQUIREMENTS. |
09/15/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/15/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
09/15/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/16/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/23/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |