Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM07095
Parcel: 12702278B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07095
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2016 ANDREW CONNOR ZONING REVIEW Approved
09/14/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/14/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/14/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
09/14/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/14/2016 ROBERT SHERRY WATER REVIEW Completed
09/14/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/14/2016 MARTIN BROWN FIRE REVIEW Approved
09/14/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2016 KROBLES1 OUT TO CUSTOMER Completed