Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM07088
Parcel: 140290290

Address:
3301 E GLOBAL LP

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07088
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: T16CM07088
Building Plan (1st Review)

TRANSMITTAL DATE: September 14, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Development package DP16-0092 will need to be revised to show the proposed generator location along with revised vehicle parking calculations. Until the development package has been revised the building plans cannot be approved.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
09/15/2016 MARTIN BROWN FIRE REVIEW Approved
09/19/2016 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL - COMMERCIAL
On Sheet E2.1B, add directional exit sign at south end of passage along west wall of Main IDF Room D0901 with arrows pointing north.
On lighting plans each light fixture has a small case letter identifying switching, for example “e”. In the same room there are two switches for “e”, labeled “e1” and “e2”. Is it intended that this signify compliance with IECC C405.2.1.2 Light Reduction Controls? If so, it is not clear what option is to be used; namely dual switching of alternate rows of luminaires, alternate rows of lamps or switching the middle lamp luminaires independently of the outer luminaires. Please clarify.
09/19/2016 FRODRIG2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/19/2016 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change STRUCTURAL CALCULATIONS
Provide structural calculations/design for gnerator slab.Reviewer: Chris Anderson,
September 15, 2016
BUILDING - COMMERCIAL
On Sheet G1.0, show vertical grab bar @ accessible toilet side view per ANSI A117.1 Figure 604.5.1.
On Sheet G3.0, plumbing fixture calculations are not compliant with Table 2902.1 based on total occupant loads for business (561 occupants) and assembly areas (223 occupants) in Code Analysis. Per formula on Table 2902.1 for business portion, 6 water closets and 5 lavatories are required for both men and women. For assembly portion 1 water closet and 1 lavatory are required for men and 2 water closets and 1 lavatory are required for women. Therefore a total of 15 water closets and 12 lavatories are required. 14 water closets with 3 urinals and 9 lavatories are provided. Proposed layout does not comply.
Regarding Sheet A4.3, per IBC 1109.2.2 at least one toilet compartment in each of the restrooms shall be wheelchair accessible and another shall be ambulatory accessible. ANSI A117.1 604.9 requires a 59” deep x 60” wide toilet compartment for an accessible water closet. A single unisex handicap accessible toilet room as an alternative does not comply with 1109.2.2 nor with the separate facilities for each sex requirement per IBC P2902.2.
The Code Analysis on Sheet G3.0 says that there will be 5 water dispensers in the facility substituted for 5 of the 7 required drinking fountains. Per IPC 410.3 water dispensers may be substituted for no more than 50% of required drinking fountains. And per DSD Policy 2008-21 (E) water dispensers must be shown on plan(s), must be connected to a permanent supply of potable water, and must have a clear floor space in compliance with ANSI A117.1 chapter 6.
On sheet A4.3, at least one urinal must be accessible per IBC 1109.2. Identify on plan and elevations which urinal will be mounted per ANSI A117.1 Fig. 605.2. All urinals are shown at the same height on elevation 10/A4.3. Are all handicap accessible?
Regarding Sheet A6.2, neither the plans on sheet A1.1A nor A4.3 show door numbers for the large restrooms. Are these doors keyed to the Door Schedule?
Regarding Sheet A6.2, courtyard gate F0600 is part of a means of egress so operating hardware must comply with IBC 1008.1.9. It is not clear that hardware set 8 reflects this IBC Section. Clarify on the hardware set description.
On Sheet S3.1, details 4 & 6/A5.8 show sunscreen 201 side panel terminating 12” above ground. Details 5 & 7/A5.8 shown sunscreen 202 side panel with HSS post terminating at ground. Do structural calculations take into account the unsupported bottom of the 201 sunscreen panel, and is detail 107 to be used for the 202 sunscreen? Clarify.
On Sheet S3.1, are thicknesses of steel plates and bars shown in details on this sheet not called out for a reason? See details 203 and 204. Contractor should not be required to review the structural calculations to locate information.
Provide structural details for generator enclosure, dumpster enclosure and courtyard steel walls with gates.
09/19/2016 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Approved
09/19/2016 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
Per DSD Policy 2008-21 (E) water dispensers substituted for drinking fountains must be shown on plan(s) and must be connected to a permanent supply of potable water.
Verify that specified lavatory faucets dispense a maximum of 0.25 gallon per metering cycle and will operate for a minimum time of 10-seconds for accessibility per amendment to IPC and ANSI A117.1.
Provide water calculations verifying that the existing water meter is adequate to accommodate total demand that the meter serves. Is there a single meter for this suite, or one meter for the whole building?
09/19/2016 FRODRIG2 WATER REVIEW Reqs Change Per DSD Policy 2008-21 (E) water dispensers substituted for drinking fountains must be shown on plan(s) and must be connected to a permanent supply of potable water.
Verify that specified lavatory faucets dispense a maximum of 0.25 gallon per metering cycle and will operate for a minimum time of 10-seconds for accessibility per amendment to IPC and ANSI A117.1.
Provide water calculations verifying that the existing water meter is adequate to accommodate total demand that the meter serves. Is there a single meter for this suite, or one meter for the whole building?

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2016 KROBLES1 OUT TO CUSTOMER Completed