Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM07032
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07032
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2016 ANDREW CONNOR ZONING REVIEW Approved
09/13/2016 ROBERT SHERRY WATER REVIEW Completed
09/13/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/13/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
09/13/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/13/2016 MARTIN BROWN FIRE REVIEW Approved
09/13/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/13/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/15/2016 RBENT2 MECHANICAL-COMMERCIAL REVIEW Needs Review