Review Details: RESUBMITTAL - TI ALL
Permit Number - T16CM07031
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/20/2017 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T16CM07031 - PLAN REVIEW COMMENTS Reviewer: Chris Anderson, January 20, 2017 BUILDING – COMMERCIAL Add architectural exterior wall section to this drawing set showing structural and finish systems proposed for roof and exterior walls. Structural framing, foundations and sheathing must match information on new structural sheets. Per previous comment 2 for sheet G1R Code Review, “the first entry indicates 1323 SF, then the occupant load is calculated using 1343 SF. Please coordinate.” Per previous comment 4 for sheet A2R, if shear wall SW1 is not to be called out on plan, add to keynote 5 “solid block all panel edges.” Per previous comment 6 for sheet A2R, keynote 3 specifies 3/8” OSB sheathing for exterior walls; however the general structural notes on new sheet S1.0R require ½” sheathing. In reference to previous comment 7 for sheet A2R, revise structural calculations and structural plan, if necessary, so that rafter sizes correspond. Structural calculations show both 2x6 and 2x8 for rafter type DJ2. Per previous comment 9 for sheet A2R, “building section 6: please cut this section on the new floor plan.” If this section is taken thru the new addition looking east, there are walls missing on the floor plan either side of the north archway. On sheet A2R, the new water heater enclosure must be constructed with continuous foundation located minimum 12” below surface of undisturbed soil width minimum width of 12”. Ref. IBC 1809.4. Indicate on structural foundation plan. On sheet G1R, the revised Index of Drawings does not match titles and sheet numbers in drawing set. On sheet A4R, show louvered door for new water heater enclosure on New South Elevation 3. On sheet S2.0R, the rooftop mechanical unit is shown in a different location than the mechanical plan on sheet M1R. On new sheet S3.0R, the post base shown on detail 108 must be either Simpson AB (or other base with 1” offset), or the post must be pressure preservative treated. Ref. IBC 2304.11.2.7. |
| 01/20/2017 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/20/2017 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Approv-Cond | ELECTRICAL – COMMERCIAL Per IECC C101.4.3 the new addition shall meet the requirements of this Code. Provide wattage calculations for the new addition per IECC C405.5.2. Remove note on sheet R-E1 and add calculations. Verify that selected interior light fixture (6@75W) complies with calculation. |
| 01/20/2017 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL – COMMERCIAL Per previous comment 3, submit heating and cooling load calculations to justify capacities of selected equipment. The output capacity of the specified heating and cooling system shall not exceed the loads calculated. Ref. IECC C403.2.1 and C403.2.2. Exhaust fan EF-1 is shown in detail 6/M2R and schedule as a ceiling mounted unit; however the architectural and structural drawings show no ceiling in the new addition. How will unit be installed and supported? |