Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM06928
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2016 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Reqs Change 1. The drilled shaft foundation for the tower is located about three feet from the existing building. Have any possible effects from the installation of the drilled shaft foundation upon the building been evaluated? Reference: Section 107.2.1, IBC 2012.
2. The USGS data used for the evaluation of the CMU equipment screen wall is for a site that is nearly ten-miles from the location of the monopalm.
09/28/2016 MARTIN BROWN FIRE REVIEW Approved
10/04/2016 STEVE SHIELDS ZONING REVIEW Approved
10/05/2016 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS
10/17/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/25/2016 LOREN MAKUS ENGINEERING REVIEW Reqs Change Clearly identify the modifications to the basin to provide the volume indicated in the drainage report.