Permit Number: T16CM06927
Parcel: 133390450

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM06927
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2016 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Completed
09/21/2016 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS
09/26/2016 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change Per AM 2-06.4.9N add a general note that incorporates the drainage reccomendations of the drainage section/statement 5.11 of the geotechnical report. This would include 2% minimum positive drainage slopes for 10 feet away from walls. Please ensure that drainage does not become trapped within the enclosure.
10/05/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/13/2017 LBOJORQ1 OUT TO CUSTOMER Completed