Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM06919
Parcel: 10511043B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM06919
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2016 ANDREW CONNOR ZONING REVIEW Approved
09/08/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify that the materials installed in the plenum conform to Section 602.2.1, IMC 2012.
2. Smoke detectors shall be located upstream of any outside air connections. Reference: Section 606.2.1, IMC 2012.
3. Verify that the installer setup menu for the specified programmable thermostat includes off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
09/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/08/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
09/08/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/08/2016 ROBERT SHERRY WATER REVIEW Completed
09/08/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the listing information for the specified backflow preventer shown in the sink drain detail and verify that the manufacturer of the valve approves of this application. Reference: Section 303.2, IPC 2012.
2. Provide specifications for the proposed sink and faucet. Reference: Section 303.4, IPC 2012.
3. Per Tucson Water, the water pressure range for this address will be greater than 80 PSI. Verify that a pressure reducing valve conforming to ASSE 1003 or CSA B356 with a strainer to reduce the water pressure to not more than 80 PSI has been installed. Reference: Section 604.8, IPC 2012.
4. Clarify how the sump pump discharge is to be terminated to the sanitary drain system. Reference: Sections 712.3.5 and 901.4, IPC 2012
5. Provide an engineered design for the use of an air admittance valve to vent a sump. Reference: Section 918.8, IPC 2012 and Section 104.11, IBC 2012.
6. PVC and ABS piping may not be used in a return air plenum. Reference: Section 602.2.1, IMC 2012.
09/08/2016 MARTIN BROWN FIRE REVIEW Approved
09/08/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed