Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM06881
Parcel: 12315164A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM06881
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/07/2017 GERRY KOZIOL WWM REVIEW Completed