Permit Number: T16CM06881
Parcel: 12315164A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM06881
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2017 ANDREW CONNOR ZONING REVIEW Approved
02/09/2017 DTAKAKI1 ENGINEERING REVIEW Approved
02/10/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/10/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide cooling/heating load calculations for the new heat pumps.
2. Show that the alterations to the building meet the requirements of IECC 2012 (i.e. REScheck).
02/10/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/10/2017 KEN BROUILLETTE FIRE REVIEW Approved
02/10/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/10/2017 ROBERT SHERRY WATER REVIEW Passed
02/16/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/16/2017 LBOJORQ1 WWM REVIEW Needs Review