Permit Number: T16CM06881
Parcel: 12315164A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM06881
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2017 MMENDIB1 BUILDING-COMMERCIAL REVIEW Needs Review
02/09/2017 MMENDIB1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/09/2017 MMENDIB1 ENGINEERING REVIEW Needs Review
02/09/2017 MMENDIB1 FIRE REVIEW Needs Review
09/07/2016 ANDREW CONNOR ZONING REVIEW Needs Review COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). Multi-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6, .9 & .10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The applicant is proposing addition to existing structures raising the height of wall to 12.9' the required set-back would be 8.514' the existing set-back is 8'