Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM06871
Parcel: 12710017D

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM06871
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change Conflicting information regarding sprinklers on cover sheet. Clarify and revise drawings, verifing travel distances, corridor ratings, etc. are appropriate for whether or not sprinklers exist.
09/22/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. What is the meaning of keynote D15.5 on sheet D1.1 (used 3 places)?
2. Provide heating and cooling load calculations that justify the capacity of the heat pump specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
3. Provide justification for basing the ventilation requirements for room 116 (Sterile) on an office occupancy rather than something like a pharmacy workroom. Show how ventilation is to be provided to this room and provide the quantity of ventilation. Note that by showing 1 CFM of supply air to the room the final result of your ventilation calculation indicates a negative number for the outside air intake. Reference: Section 403.3, IMC 2012.
4. Explain the purpose of the transfer duct that appears to move air from the conference room to the passage (corridor) when fan EF-2 is not operating. Reference: Section 107.2.1, IBC 2012.
09/22/2016 ROBERT SHERRY WATER REVIEW Completed
09/23/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/27/2016 FRODRIG2 BUILDING-COMMERCIAL REVIEW Needs Review