Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM06870
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/07/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 09/12/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 09/12/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide cooling/heating load calculations. 2. Revise the sequence of operation of the restroom exhaust fan. 3. Revise the AC system to avoid using the corridor as a duct. |
| 09/12/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Please provide complete compliance with the 2012 IECC for the interior lighting. #2. Provide a complete luminaire schedule. Ref: 2012 IBC sec. 107.2.1, 2012 IECC, 2011 NEC. |
| 09/12/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 09/12/2016 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SPECIFY POST BASE HARDWARE 2. PROVIDE STRUCTURAL CALCULATIONS FOR NEW ROOF BEAM |
| 09/12/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/12/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/12/2016 | CTREVIL1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/19/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |