Permit Number: T16CM06870
Parcel: 12108067D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM06870
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
09/12/2016 ANDREW CONNOR ZONING REVIEW Approved
09/12/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide cooling/heating load calculations.
2. Revise the sequence of operation of the restroom exhaust fan.
3. Revise the AC system to avoid using the corridor as a duct.
09/12/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Please provide complete compliance with the 2012 IECC for the interior lighting.
#2. Provide a complete luminaire schedule.
Ref: 2012 IBC sec. 107.2.1, 2012 IECC, 2011 NEC.
09/12/2016 KEN BROUILLETTE FIRE REVIEW Approved
09/12/2016 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change 1. SPECIFY POST BASE HARDWARE
2. PROVIDE STRUCTURAL CALCULATIONS FOR NEW ROOF BEAM
09/12/2016 ROBERT SHERRY WATER REVIEW Completed
09/12/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/12/2016 CTREVIL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2016 KROBLES1 OUT TO CUSTOMER Completed