Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T16CM06828
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | 1. SHEET A5.0; ELEVATION 11: PLEASE INDICATE ON THE DRAWING HOW THE NEW WATER HEATER IS SUPPORTED ON THE WALL. INCLUDE MEMBER SIZES, CONNECTOR SIZES AND QUANTITIES. |
| 03/27/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide ventilation for the new pet wash room. Reference: Section 403.3, IMC 2012. |
| 03/27/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/27/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show how the common venting of the two pet tubs, the mop sink, and the trench drain complies with Section 911.3, IPC 2012. Reference: Section 709.1, IPC 2012. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/29/2017 | MMENDIB1 | OUT TO CUSTOMER | Completed |