Permit Number: T16CM06828
Parcel: 138243950

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T16CM06828
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. SHEET A5.0; ELEVATION 11: PLEASE INDICATE ON THE DRAWING HOW THE NEW WATER HEATER IS SUPPORTED ON THE WALL. INCLUDE MEMBER SIZES, CONNECTOR SIZES AND QUANTITIES.
03/27/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide ventilation for the new pet wash room. Reference: Section 403.3, IMC 2012.
03/27/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/27/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how the common venting of the two pet tubs, the mop sink, and the trench drain complies with Section 911.3, IPC 2012. Reference: Section 709.1, IPC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2017 MMENDIB1 OUT TO CUSTOMER Completed