Permit Number: T16CM06783
Parcel: 14109020A

Address:
6711 E BENSON HY

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM06783
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2016 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS
09/21/2016 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Reqs Change The structural calculations included with this activity are for the cell tower installation located at 9444 E Golf Links Road (T16CM05505). Provide the correct structural calculations.
09/22/2016 ANDREW CONNOR ZONING REVIEW Approved
09/27/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref: Plan Sheets T1, C2, C3.
These plan sheets make reference to a 100 amp service to be replaced with a 200 amp service. Please provide a complete one line diagram showing all the proposed electrical service and associated equipment. Include grounding, feeder conduits/conductor sizes and types, AIC rating of equipment, Complete load calc's, Panel schedules, voltage, phase, etc. As required per the City of Tucson COMMERCIAL PLAN SUBMITTAL REQUIREMENTS ( electrical ). This can be downloaded from www.tucsonaz.gov/pdsd.
Ref; 2012 IBC sec.107.2.1, 2011 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2016 KROBLES1 OUT TO CUSTOMER Completed