Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM06757
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/02/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 09/02/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/02/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A0.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 2. SHEET A1.0; PARTITION LEGEND: FOR NEW WALLS THAT INDICATE BRACING AT THE TOP OF THE WALL, PLEASE PROVIDE THE BRACING SIZE, AND INDICATE THE SIZE AND QUANTITY OF CONNECTORS AT THE TOP OF THE PARTITION AND AT THE STRUCTURE ABOVE. PROVIDE DETAILS ON DRAWINGS AS REQUIRED. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 09/02/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/02/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/06/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 09/06/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/06/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/06/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The lavatory metering faucet shall deliver a maximum of 0.25 gallons per cycle. 2. The thermostatic mixing valve shall be listed to ASSE 1070. |