Permit Number: T16CM06690
Parcel: 12620001C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM06690
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The new general notes for the windows on sheet a8.2 call for a SHGC of 0.31 but the energy calculations are based on a SHGC of 0.23. Coordinate the maximum SHGC allowed for the windows. [Second comment: Include the required NFRC-certified U-values and solar heat gain factors for the revised windows on the drawings. [Initial comment: Coordinate the window specifications shown on the energy code analysis for the building envelope with the window descriptions shown on the drawings (i.e. include the required NFRC-certified U-values and solar heat gain factors on the drawings). Reference: Section C103.2, IEC 2012.]
01/03/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/23/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved