Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T16CM06673
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font to have a minimum size of 3/32". 2. The water supply to the flush valve water closet will result in a water velocity greater than 8 feet per second. 3. Provide a code analysis to verify the correct number of plumbing fixtures have been proposed, 4. Correct detail 1/P2.0 to provide a separate indirect waste line for each sink compartment. 5. Correct detail 3/P2.0 to provide separate indirect drain lines from the ice cuber condensate drain and the ice bin drain. 6. Verify that discharge from the glass washer is less than 140 degrees Fahrenheit. 7. What is P15? 8. Show how the proposed restroom is accessible (e.g. see the location of the wtre heater). 9. Provide specifications or required standards (e.g. NSF) for all plumbing fixtures. 10. Verify that the lavatory faucet is set to deliver a maximum of 0.25 gallons per cycle and that the cycle will last for at least 10 seconds. |