08/30/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
2. Show the size, routing, and termination of the condensate drain for the water source heat pumps. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
3. Provide an auxiliary or secondary condensate drain system. Reference: Section 307.2.3, IMC 2012.