Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM06652
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/29/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
08/29/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
08/30/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/30/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. 2. Show the size, routing, and termination of the condensate drain for the water source heat pumps. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. 3. Provide an auxiliary or secondary condensate drain system. Reference: Section 307.2.3, IMC 2012. |
08/30/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/30/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/30/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
08/30/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
08/31/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/06/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |