Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM06648
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 08/29/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 08/30/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/30/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. 2. Show the size, routing, and termination of the condensate drain for WSHP 1.1. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. 3. Provide an auxiliary or secondary condensate drain system. Reference: Section 307.2.3, IMC 2012. 4. Clarify the termination of exhaust fan EF-1.1 - it appears to be directed onto a walkway. Reference: Section 501.3.1.1, IMC 2012. |
| 08/30/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/30/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/30/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the metering faucets for the lavatories will limit the amount of water dispensed to no more than 0.25 gallons per cycle and that each cycle will last at least 10 seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. |
| 08/30/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/31/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/06/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |