10/18/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM06558
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. Update the seal expiration, all architectural sheets.

FLOOR PLANS:

1. The garage window is not compliant with egress, R310. Update keynote #10 this location.

PLUMBING PLANS:

1. Locate above ground LP gas containers a minimum of 5 feet from buildings and property lines, IFC 6104.3. Update the location of keynote #36, sheet a3.1.

ELECTRICAL PLANS:

1. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14.