Permit Number: T16CM06553
Parcel: 112062360

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T16CM06553
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The water calculations on sheet P2.0 show a demand of 26 GPM. The maximum flow rate allowed by Tucson Water for a 3/4" water meter is 22.5 GPM. Verify theat Tucson Water will allow a 3/4" meter to be used with this demand.
11/29/2016 ROBERT SHERRY WATER REVIEW Reqs Change The water calculations on sheet P2.0 show a demand of 26 GPM. The maximum flow rate allowed by Tucson Water for a 3/4" water meter is 22.5 GPM. Verify theat Tucson Water will allow a 3/4" meter to be used with this demand.
11/30/2016 KROBLES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/30/2016 KROBLES1 OUT TO CUSTOMER Completed