Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM06553
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/24/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide calculations to show that the HVAC system can accommodate the heat and moisture generated by the dish washer and that a Type II hood will not be required. |
| 08/24/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Printing errors on electrical plans. |
| 08/24/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 08/24/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1.0; CODE REVIEW (EXITING PLAN): THE REQUIREMENTS FOR THE DISTANCE BETWEEN EXITS PER 1015.2.1 ARE NOT MET FOR THE EXITS SHOWN. IF THE BACK EXIT CAN BE USED, IT WILL MEET THOSE SEPARATION REQUIREMENTS. PLEASE VERIFY AND INDICATE ON THE PLAN. 2. SHEET A1.0; CODE REVIEW (ALLOWABLE AREA): IS THIS BUILDING SPRINKLERED? THE BUILDING SUMMARY INDICATES NO, BUT THE ALLOWABLE AREA CALCULATION USES A SPRINKLER INCREASE PER SECTION 506.3 (CAN BE INCREASED BY 300%). IF NOT SPRINKLERED, THE ALLOWABLE AREA WILL BE LESS THAN THE ACTUAL AREA FOR THE ENTIRE BUILDING. PLEASE CLARIFY. 3. SHEET A1.0; CODE REVIEW (GOVERNING REGULATIONS): PLEASE REVISE THE ACCESSIBILITY CODE TO THE 2009 ICC/ANSI A117.1. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 08/24/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/24/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The water pressure data from Tucson Water indicates that the pressure may exceed 80 PSI. Provide a pressure regulator. 2. Show the hot water return piping on the plumbing plan. |
| 08/31/2016 | KROBLES1 | FIRE | REVIEW | Needs Review | |
| 08/31/2016 | KROBLES1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/31/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |