Permit Number: T16CM06505
Parcel: 134100870

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T16CM06505
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2017 ARUIZ1 ENGINEERING REVIEW Needs Review
08/07/2017 ARUIZ1 BUILDING-RESIDENTIAL REVIEW Needs Review
09/12/2016 ANDREW CONNOR ZONING REVIEW Needs Review COMMENTS: the following comments are relative to an application for a variance.


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The minimum setback to a side street property line is ten (10) feet (UDC Section 6.4.5.C.1.b).

The applicant is proposing a 0' side street set-back for an attached garage and a 0' set-back on North and East property lines for a detached garage
09/12/2016 ANDREW CONNOR NPPO REVIEW Passed
09/12/2016 ANDREW CONNOR ZONING REVIEW Needs Review CDRC TRANSMITTAL

FROM: Steve Shields,
Lead Planner


PROJECT:
T16CM06505
8131 E. Malvern Street
Permit existing attached two (2) car garage, detached one (1) car garage and detached carport in the front yard.

TRANSMITTAL:
COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Section 3.10.1).

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 9'-10" the required perimeter yard setback from the one (1) car garage to the north and west property line is 6'-6", proposed perimeter yard is 0'-0".

The minimum setback to a side street property line is ten (10) feet (UDC Section 6.4.5.C.1.b). Proposed side street perimeter yard setback to the two (2)car garage and detached carport is 0'-0".

The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a). Based on a height 9'-6" the required front street perimeter yard from the detached carport is 20'-0" proposed front street perimeter yard is 0'-0"

The minimum setback to the back of a sidewalk for a garage is nineteen (19) feet (UDC Section 6.4.5.C.2.b.1). The minimum driveway length for a garage is eighteen feet to the property line (UDC Section 6.4.5.C.2.b.1.a & b.). The proposed setback from the detached carport to the sidewalk is 0'-0"

Per UDC Section 6.6.3.B Detached accessory buildings are not permitted in the buildable area extending the full width of the lot between the principal building and the front street lot line, except for terraces and steps not over three feet high above the natural grade, paved areas, and fences or walls. The detached carport does not meet this standard.