Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM06498
Parcel: 117062960

Address:
416 E 9TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM06498
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/06/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/07/2016 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2016 KROBLES1 OUT TO CUSTOMER Completed