Permit Number: T16CM06498
Parcel: 117062960

Address:
416 E 9TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM06498
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change Still waiting for building issues to get resolved-kenb
08/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change All vents (except for vents serving interceptors located outdoors) shall rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012. [Initial comment: Provide a vent downstream of the gravity grease separator to protect the seal for the grease separator. Reference: Section 1003.9, IPC 2012.]
08/29/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A2; EXITING: IF ONLY ONE EXIT IS PROVIDED (PER RESPONSE TO PREVIOUS COMMENT 3), THE COMMON PATH OF EGRESS TRAVEL MUST MEET THE DISTANCES INDICATED IN THE IBC TABLE 1014.3 (MAXIMUM 75 FEET). PLEASE INDICATE ON THE PLAN THE COMMON PATH OF EGRESS TRAVEL (MEASURED PER IBC SECTION 1016.3) MEETS THE TABLE REQUIREMENTS.
2. PREVIOUS COMMENT 4: PLEASE INCLUDE THE STRUCTURAL MODIFICATION ON THE FULL SIZE DRAWINGS.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/29/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved