Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM06498
Parcel: 117062960

Address:
416 E 9TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM06498
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
08/22/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/22/2016 ANDREW CONNOR ZONING REVIEW Approved
08/22/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/22/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1; BUILDING CODES: THE BUILDING AREA FOR THIS TI INDICATES 1166 SF. THE OCCUPANT LOAD IS BASED ON 708 SF. PLEASE INDICATE ON THE DRAWINGS HOW THE 708 SF WAS ESTABLISHED.
2. SHEET A1; BUILDING CODES: PLEASE INDICATE THE ACTUAL USE AS A-2, BUT THE IBC SECTION 303.1.1 ALLOWS A GROUP B CLASSIFICATION (LESS THAN 50 OCCUPANTS).
3. SHEET A1; BUILDING CODES: THE EXITS INDICATE ONE, WHILE THE DRAWINGS INDICATE TWO. PLEASE CLARIFY.
4. GENERAL: THE STRUCTURAL CALCULATIONS PROVIDED INDICATE ADDITIIONS TO THE EXISTING ROOF TRUSSES AT THE NEW MECHANICAL UNIT ARE REQUIRED. PLEASE INDICATE ON THE FULL SIZE DRAWINGS THOSE REQUIRED REVISIONS.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/22/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. A ware washer is to discharge through a gravity grease interceptor but may not discharge through a hydromechanical grease interceptor. Verify how the discharge from the dishwasher can be accommodated with the Pima County Regional Wastewater Reclamation Department. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
2. Provide a vent downstream of the gravity grease separator to protect the seal for the grease separator. Reference: Section 1003.9, IPC 2012.
3. Verify that the discharge from the ware washer (kitchen equipment number 3) will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012.
08/22/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/22/2016 ROBERT SHERRY WATER REVIEW Completed New 3/4" meter
08/23/2016 MARTIN BROWN FIRE REVIEW Reqs Change SAME AS BUILDING COMMENTS